Department of
Community Affairs
Division of Fire Safety

BULLETIN: 2009-1
SUBJECT: Subchapter
4 Retrofit Requirements for Nightclubs
REFERENCE: N.J.A.C. 5:70-4.1(b) 2, N.J.A.C.
5:70-4.7(a),
N.J.A.C.
5:70-4.9(a) 9, N.J.A.C. 5:70-4.11(f) 3, and
N.J.A.C.
5:70-4.11(g) 1 and 2
ISSUE DATE: March 6, 2009
This Bulletin is
intended to provide guidance concerning the retrofit requirements for
nightclubs as required by Subchapter 4, which are to be completed by February 5,
2009.
The New Jersey
Uniform Construction Code defines a nightclub as follows, “Use Group A-2
(Nightclubs)”: This Use Group shall include all buildings and spaces of public
assembly, designed for use as dance halls, nightclubs, and eating and/or
drinking establishments, and similar occupancies, in which the established
maximum permitted occupant load exceeds the number of seats provided by more
than 30 percent or which affords less than 12 square feet net area per
occupant. For purposes of determining the net area per occupant, only the actual
public assembly room or rooms shall be considered. For purposes of applying the
requirements of this chapter, the nightclub shall include all rooms, lobbies,
and other spaces connected thereto with a common means of egress and entrance.
Two key points
need to be looked at in determining whether or not an assembly space is a
nightclub. The Fire Official must review
the space for either of the two conditions listed below:
1. The first consideration is when the
maximum occupant load exceeds the amount of seats by 30%. For example, if the
maximum occupant load of the building is calculated at 15 square foot net per
person totaling 500 occupants, the number of seats provided would need to be at
least 350 or more. If there are less than 350 seats, the space would be
considered a nightclub.
2. The second part to consider is whether
the net square footage affords less than 12 square foot per person. The Fire
Official must verify the occupant load for each assembly space. To determine
this, any area which is non-occupiable space must be deducted from the square
footage calculations, only the actual occupiable space should be used in the
square footage calculations. Some examples of non-occupiable spaces would
include: thickness of walls, coat rooms, entertainment stages or platforms,
closets, fireplaces, pool tables, bathrooms or bars and the serving areas
behind a bar. The Fire Official must start with the gross area of the building
and deduct the non-occupiable spaces or areas to determine the net floor area.
When determining the total occupant load of the nightclub for the
examples above you must include all rooms, lobbies and other spaces that share
a common means of entrance and egress. The Fire Official must verify the net
occupant load for each room or space that may be occupied if the same entrance
or exit are shared.
Once it is
determined that a building or portion thereof is a nightclub, the applicable
retrofit provisions will be based upon any of following: 1) the location of the
nightclub in the building; 2) the maximum permitted occupancy of the nightclub;
or 3) the square footage of the building or area in use. The applicable
portions of Subchapter 4 include fire suppression, automatic fire alarms and
means of egress.
I. Fire Suppression
N.J.A.C. 5:70-4.7
(a) All buildings of Use Group A-2 (nightclubs) or portions thereof
when separated in accordance with (l) below shall be equipped throughout with
an automatic fire suppression system installed in accordance with the New
Jersey Uniform Construction Code where any of the conditions in (a) 1, 2 or 3
below exist:
1. The A-2 (nightclub) Use or portion
thereof is located on a floor other than the level of exit discharge. For
purposes of applying this paragraph, the level of exit discharge shall be defined
as having all exits discharging not more than five feet above, nor more than
two feet below, the adjacent grade:
2. The building or portion
thereof has an occupant load of 300 or more:
i. Voluntarily limiting the occupant load
in a space that will accommodate a greater number shall not be permitted for
purposes of determining whether suppression is required. The nightclub space
itself may be reduced to a size such that the occupant load calculated in
accordance with Table 5:70-4.11(f)3 at N.J.A.C. 5:70-4-11(f)3 is fewer than
300. If this option is chosen, then the following conditions shall apply:
(1) The nightclub space shall be separated
from the other portions of the building through the use of one hour fire
resistance rated assemblies constructed in accordance with the building subcode
of the Uniform Construction Code (N.J.A.C. 5:23-3.14);
(2) Opening protectives constructed in
accordance with the building subcode shall be required for all openings between
accessory use areas and the nightclub space. For purposes of applying these
requirements, accessory use areas shall include, but not be limited to, all
back of house spaces, storage rooms, offices, kitchens and coatrooms. Accessory
use areas shall not include any assembly spaces;
(3) No openings shall be permitted between
any non-accessory use areas and the nightclub;
(4) The separated, non-accessory portions
of the building shall not contain any assembly uses; and
(5) The means of egress serving any
separated, non-accessory portions of the building and the means of egress
serving the nightclub shall be totally independent of one another.
(A) Exception:
Means of egress shared between a nightclub and a separated, non-accessory space
shall be permitted for nightclubs located in buildings of Use Group R-1; or
3. The building or portion thereof exceeds 5,000
square feet.
4. The automatic fire
suppression system shall be tied to the performance sound system and to the
house lights in such a way that activation of the fire suppression system mutes
the performance sound system and restores the intensity of illumination to that
required by N.J.A.C. 5:70-4.11(i)2.
If the nightclub
use meets any of the above conditions, an automatic fire suppression system is
required to be installed in the building or nightclub use unless it meets the
provisions of section 2. In order to accept a reduced occupant load under
section (a)2, the business or building owner must apply for and receive
construction permits under the Uniform Construction Code and a new Certificate
of Occupancy, indicating the new occupant load shall be provided. Physically
reducing the occupant load will not exempt the use from other retrofit
provisions as detailed below, unless the new occupant load is under the listed
thresholds.
Section (l)
requires that the use requiring suppression be completely separated from the
remaining portions of the building by a minimum of a one hour fire resistive
construction, otherwise the entire building must be provided with the required
suppression.
It is important
to note that activation of the fire suppression system immediately mutes the
sound system and brings house lights back up to the minimum required levels for
egress. This would include any permanently installed sound systems as well as
any sound equipment brought in by outside performers.
Monitoring of the
fire suppression system will be accomplished by using one of the methods listed
in N.J.A.C. 5:70-4.7(k), as required by the Fire Official. Further guidance on
system monitoring is provided in Bulletin 2006-02.
II. Automatic Fire Alarms
N.J.A.C. 5:70-4.9
(a) An automatic fire alarm system shall be installed as required
below in accordance with the New Jersey Uniform Construction Code.
9. In all buildings or portions thereof of Use Group A-2
(nightclubs) with an occupant load of 100 or more that are not otherwise
required to have an automatic fire suppression system.
i. If the alarm is activated by smoke
detectors, it shall be activated by either two cross-zoned smoke detectors
within a single area or a single smoke detector monitored by an alarm
verification zone or an approved equivalent method and the smoke detectors
shall be of a type designed to reduce the possibility of false notifications
based on the conditions present in the area protected.
ii. The automatic fire alarm system shall
be tied to the performance sound system and to the house lights in such a way
that activation of the fire suppression system mutes the performance sound
system and restores the intensity of illumination to that required by N.J.A.C.
5:70-4.11(i)2.
Nightclubs with
an occupancy of 100 up to 299 persons, are required to have an automatic fire
alarm system installed as required above. This would include any premises that
reduced its occupant load using N.J.A.C. 5:70-4.7(2)i.
It is important
to note that activation of the fire alarm system immediately mutes the sound
system and brings house lights back up to the minimum required levels for
egress. This would include any permanently installed sound systems as well as
any sound equipment brought in by outside performers.
Monitoring of the
fire alarm system will be accomplished by using one of the methods listed in
N.J.A.C. 5:70-4.7(k), as required by the Fire Official. Further guidance on
system monitoring is provided in Bulletin 2006-02.
III. Means of Egress
N.J.A.C. 5:70-4.11
(f)3 The maximum permitted occupant load of a given space shall be
determined by dividing the floor area for a given use by the occupant load
factor in Table 5:70-4.11(f)3.
i. Except in Use Group A-2 (nightclubs),
the occupant load may be equal to the total number of occupants for whom exit
capacity if provided by (f)1 above. The resulting total occupant load shall not
exceed one occupant per five square feet of net floor area over the entire use.
(g) All buildings of Use Group A with an
occupant load of 100 or more shall be provided with a main entrance capable of
serving as the main exit with an egress capacity for at least one-half the
total occupant load. The remaining exits shall be capable of providing
two-thirds of the total required exit capacity.
1. For Use Group A-2 (nightclubs), the
main exit and at least one remaining exit shall be placed a distance apart
equal to one-half the length of the maximum overall diagonal distance of the
area served in buildings not equipped throughout with an automatic fire
sprinkler system and one-third the maximum overall diagonal distance of the
area served in building or portions thereof that are equipped throughout with
an automatic fire sprinkler system.
2. Use Group A-2 (nightclub) buildings or
portions thereof with an occupant load of more than 300 shall have a main
entrance capable of serving as the main exit with an egress capacity for at
least two-thirds of the total occupant load. The remaining exits shall also be
capable of providing two-thirds of the total required exit capacity.
As we have seen
many times, overcrowding and insufficient and improperly placed exits have
contributed to many of the fatalities and injuries associated with fires in
places of assembly. These provisions are intended to ensure a safe occupant
load is in place and that there are sufficient and properly placed exits
available for use.
For example, (g)1
provides for a space with a diagonal distance of 300 feet, that the main
entrance and at least one exit must be at least 150 feet apart in a nightclub
without an automatic fire suppression system; at least 100 feet apart in
nightclubs provided with automatic fire suppression.
Section (g)2
would require a nightclub with an occupancy of 600 to have a main entrance/exit
capable of handling 400 people and the remaining exits in the nightclub must
also accommodate at least 400 people.
Please note: It
is reasonable for an establishment to take up to six or more months to comply
with the newly mandated requirements; therefore, consideration should be given
to allow the establishment sufficient time to comply with a violation of these
retrofit requirements. During this period of time the business will need to perform
design work, apply for permits, select and hire a contractor and complete the work including
obtaining any necessary Uniform Construction Code inspections and approvals. It
is recommended that the Fire Official follow the process closely and grant appropriate
extensions of time as needed.
Any questions regarding this
bulletin should be directed to the Division of Fire Safety, Bureau of Fire Code
Enforcement at 609-633-6132.